How it is worked out
Equivalent diameter = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25
A worked example
A 12 by 8 inch duct is equivalent to a round duct of about 10.7 inches, so a 10 inch round is a little small and a 12 inch has room to spare.
Good to know
- Keep the aspect ratio under about 4 to 1. Flat, wide ducts are noisy and waste fan power.
- Round to the next standard size up, not down.
- Sizing ducts for a system should follow a proper duct design method.
How we know this calculator is right
Before this calculator went on the site, 5 answers were worked out separately from its code, by hand or straight from the formula above. Each time this page loads, your own browser runs the calculator on those same numbers and compares. Turn on JavaScript to see the comparison.
See every check
| Numbers used | Result | Worked out separately | This calculator |
|---|