Airflow heat calculator

Enter the airflow and the temperature difference between supply and return air to find how much heat the air is carrying.

Example: You measured 400 CFM and a 20 degree split at a furnace and want to know what it is really delivering.

Your numbers

Measure the temperature of the air going into the unit and coming out of it. The difference is the temperature split.

CFM
°F
  • Sensible heat0
  • In tons0
  • In kilowatts0

How it is worked out

BTU per hour = 1.08 × CFM × temperature difference

The 1.08 comes from the weight of air and the heat it takes to warm it, for air at sea level and normal room conditions.

A worked example

Four hundred CFM with a 20 degree split is 1.08 × 400 × 20, which is 8,640 BTU per hour, or 0.72 tons.

Where this turns up

  • Checking what a furnace is really putting into the air, from the measured airflow and temperature rise.
  • Working backwards to airflow. If you know the furnace output and the temperature rise, CFM is output ÷ (1.08 × rise).
  • Finding how much heating a ventilation fan adds to the load when it brings in cold outside air.

This is sensible heat only, the part you can measure with a thermometer. Air conditioning also removes moisture, which is latent heat, so the total cooling is higher than this figure. At altitude the 1.08 is lower.

Common questions

What split should I expect?

Many technicians look for roughly 16 to 22 degrees across a cooling coil, but it depends on humidity and airflow. Follow the equipment data.

How we know this calculator is right

Before this calculator went on the site, 6 answers were worked out separately from its code, by hand or straight from the formula above. Each time this page loads, your own browser runs the calculator on those same numbers and compares. Turn on JavaScript to see the comparison.

See every check
Numbers usedResultWorked out separatelyThis calculator

What this proves: the calculator does the arithmetic of the formula shown, correctly. What it cannot prove: your measurements, or figures such as coverage per bag, waste and spacing, which are typical starting values you can change. Go by the product label and your local code.

Used by: hvac technicians.