kVA to amps calculator

Full-load current of a transformer or generator from its kVA rating.

Example: You want the secondary current of a 75 kVA transformer for the paperwork.

Your numbers

Use the line-to-line voltage for three-phase.

kVA
V
  • Full-load current0
  • In volt-amps0

How it is worked out

Three-phase: amps = kVA × 1,000 ÷ (1.732 × volts)

Single-phase: amps = kVA × 1,000 ÷ volts

A worked example

A 75 kVA three-phase transformer at 480 volts: 75,000 ÷ (1.732 × 480) is 90.2 amps.

Good to know

  • This is the nameplate full-load current. Sizing conductors and protection from it is a code calculation.

How we know this calculator is right

Before this calculator went on the site, 3 answers were worked out separately from its code, by hand or straight from the formula above. Each time this page loads, your own browser runs the calculator on those same numbers and compares. Turn on JavaScript to see the comparison.

See every check
Numbers usedResultWorked out separatelyThis calculator

What this proves: the calculator does the arithmetic of the formula shown, correctly. What it cannot prove: your measurements, or figures such as coverage per bag, waste and spacing, which are typical starting values you can change. Go by the product label and your local code.