How the spacing is worked out
The distance between the two bends is the offset height multiplied by a figure for the angle. That figure is the cosecant of the angle, which is why electricians memorise it as a table.
Distance between bends = offset height × multiplier
- 10 degrees: multiplier 5.76 (often rounded to 6), shrink 1/16 inch per inch of offset
- 22.5 degrees: multiplier 2.61, shrink 3/16 inch
- 30 degrees: multiplier 2.00, shrink 1/4 inch
- 45 degrees: multiplier 1.41, shrink 3/8 inch
- 60 degrees: multiplier 1.15, shrink 1/2 inch
A worked example
For a 6 inch offset with 30 degree bends, the marks go 12 inches apart. The conduit ends up 1½ inches shorter along its run, so move the first mark that much further from the box if you are bending toward an obstacle.
Good to know
- Shallower bends are easier to pull wire through. Steeper bends save space. Codes limit the total bends between pull points to 360 degrees.
- Keep both bends in the same plane, or the offset comes out twisted. Sight down the conduit before the second bend.
- Shrink figures are the standard hand-bender values and are close approximations.
Common questions
Does conduit size matter?
Not for the spacing. The multipliers are the same for every size. What changes is the bender and its take-up marks.
How we know this calculator is right
Before this calculator went on the site, 13 answers were worked out separately from its code, by hand or straight from the formula above. Each time this page loads, your own browser runs the calculator on those same numbers and compares. Turn on JavaScript to see the comparison.
See every check
| Numbers used | Result | Worked out separately | This calculator |
|---|
What this proves: the calculator does the arithmetic of the formula shown, correctly. What it cannot prove: your measurements, or figures such as coverage per bag, waste and spacing, which are typical starting values you can change. Go by the product label and your local code.